基于高频天平测力试验的500kV单回路输电塔风致响应研究

  • 张庆华1,2,顾明2
作者信息 +

WIND-INDUCED RESPONSE OF 500kV SINGLE-CIRDUIT TRANSMISSION TOWER BASED ON HIGH FREQUENCY FORCE BALANCE TESTS

  • ZHANG Qinghua1,2, GU Ming2
Author information +
文章历史 +

摘要

基于高频测力天平风洞试验的结果,采用平稳激励下随机振动的模态叠加法,计算了典型500kV单回路酒杯型输电塔的风致响应。结果表明:输电塔结构顺风向和横风向脉动位移响应、加速度和基底弯矩值都较大,横风向响应值甚至大于顺风向。各个方向一阶振型在响应中起主导作用。位移阵风响应因子和基底弯矩响应因子随风向变化趋势相近,顺风向关键节点位移响应因子最大值不超过1.8,弯矩响应因子约为1.5。

Abstract

Wind-induced responses of a 500kV single-circuit transmission tower are computed based on wind forces acting on the tower obtained from wind tunnel tests using high-frequency-force-balance technique in a wind tunnel and the modal decomposition method. The results show that the dynamic displacements,accelerations and base bending moments (BBM) are all large in both along and across wind directions, and furthermore, the across wind dynamic responses are generally larger than the along wind responses. The first mode has dominant contributions to the total responses respectively in both A and B directions. In addition, gust response factors corresponding to displacement and BBM have similar trends. The maximum displacement gust response factors of critical nodes are no more than 1.8, and the maximum moment gust response factors are about 1.5.


关键词

输电塔 / 风洞试验 / 模态叠加法 / 风致响应 / 阵风响应因子

Key words

transmission tower / wind tunnel test / modal decomposition method / wind-induced response / gust response factor