When the HVDC system works in monopole ground return mode, dc current flows through the neutral of ac power transformer with the neutral grounded, which will enhance its vibration . In the debugging of the Yibin-Jinhua high voltage direct current (HVDC) system, the vibration testing system was applied by the researchers to detect the vibration signal of the 500kV transformer in the Luzhou substation, which is nearby the grounding substation. The spectrum distribution of the transformer vibration signal is analyzed by means of the wavelet transform, the vibration acoustic fingerprint and three typical characteristic parameters including the distribution percentage of spectral energy、the energy radio of odd and even harmonic and the waveform distortion radio, are extracted respectively. When the current of HVDC system increased from 0A to 5000A, the impact of the DC bias on the operation status of 500kV transformer was investigated through the change analysis of the vibration acoustic fingerprint and three characteristic parameters. It indicated that the energy radio of odd and even harmonic of the 500kV transformer vibration signal induced significantly with the increase of the current. In addition, the distribution percentage of spectral energy and the vibration acoustic fingerprint changed obviously. It is conducive to assess accurately the effect of the DC bias on the operation status of the transformer.
Ding Deng-wei, Zhang Xin-hai and Lan xin-sheng .
Effect Investigation of Vibration on 500kV AC Transformer Caused by HVDC System under Monopole Operation[J]. Journal of Vibration and Shock, 2016, 35(17): 201-206
{{custom_sec.title}}
{{custom_sec.title}}
{{custom_sec.content}}
参考文献
[1] C. Bartoletti, M. Desiderio, D. D. Carlo, G. Fazio, F. Muzi, G. Sacerdoti and F. Salcatori. “Vibro-acoustic techniques to diagnose power transformers” , IEEE Trans. Power Del, Vol. 19, No. 1, pp. 221–229, 2004.
[2] Belén García, Juan Carlos Burgos and Ángel Matías Alonso. “Transformer Tank Vibration Modeling as a Method of Detecting Winding Deformations—Part I:Theoretical Foundation”, IEEE Trans. Power Del, Vol. 21, No. 1, pp. 157–163, 2006.
[3] Belén García, Juan Carlos Burgos and Ángel Matías Alonso. “Transformer tank vibration modeling as a method of detecting winding deformations-part II experimental verification”, IEEE Trans. Power Del, Vol. 21, No. 1, pp. 164–169, 2006.
[4] Cipriano Bartoletti, Maurizio Desiderio and Danilo Di Carlo. “Vibro-acoustic techniques to diagnose power transformers”, IEEE Trans. Power Del, Vol. 19, No. 1, pp. 221–229, 2004.
[5] Sebastian Borucki. “Diagnosis of Technical Condition of Power Transformers Based on the Analysis of Vibroacoustic Signals Measured in Transient Operating Conditions”, IEEE Trans. Power Del, Vol. 27, No. 2, pp. 670–676, 2012.
[6] Pengfei Shao, Longfu Luo and Yong Li. “Electromagnetic Vibration Analysis of the Winding of a New HVDC Converter Transformer”, IEEE Trans. Power Del, Vol. 27, No. 2, pp. 123–130, 2012.
[7] Tom Hilgert, Lieven Vandevelde, and Jan Melkebeek. “Comparison of Magnetostriction Models for Use in Calculations of Vibrations in Magnetic Cores”, IEEE Trans. magn, Vol. 44, No.6, pp. 874–877, 2008.
[8] 骆 波,王丰华,廖天明,等.应用改进复Morlet小波识别电力变压器绕组模态参数[J].振动与冲击,2014,33(6):131-136.
LUO Bo,WANG Feng-hua,LIAO Tian-ming,et al.Modal parameters identification of power transformer winding based on the improved complex Morlet wavelet[J].Journal of Vibration and Shock,2014,33(6):131-136.
[9] Jinliang He, Zhanqing Yu, Rong Zeng and Bo Zhang. “Vibration and Audible Noise Characteristics of AC Transformer Caused by HVDC System Under Monopole Operation”, IEEE Trans. Power Del, Vol. 27, No. 2, pp. 1835–1842, 2012.
[10] 赵志刚,刘富贵,张俊杰,等.直流偏磁条件下变压器励磁电流的实验与分析[J].电工技术学报,2010,25(4):71-76.
Zhao Zhigang,Liu Fugui,Zhang Junjie,et al.Measurement and analysis of magnetizing current in DC-biased transformers[J] .Transactions of China Electrotechnical Society,2010,25(4):71-76(in Chinese).
[11] 赵志刚,刘富贵,程志光,等.HVDC 中直流偏磁电力变压器叠片铁心损耗及磁通分布[J].高电压技术,2010,36(9):2346-2351.
Zhao Zhigang,Liu Fugui,Cheng Zhiguang,et al.Loss and flux distribution of power transformer laminated core under DC-biased magnetization condition in HVDC[J].High Voltage Engineering,2010,36(9):346-2351(in Chinese).
[12] 郭满生,梅桂华,刘东升,等.直流偏磁条件下电力变压器铁心B_H 曲线及非对称励磁电流[J].电工技术学报,2009,24(5):46-51.
Guo Mansheng,Mei Guihua,Liu Dongsheng,et al.B-H curve based
on core and asymmetric magnetizing current in DC-biased transformers[J].Transactions of China Electrotechnical Society,2009,24(5):46-51(in Chinese).
[13] 朱林,韦晨,余洋.单相变压器的直流偏磁励磁电流问题及其对保护的影响分析[J].电力系统保护与控制,2010,38(24):158-162.
Zhu Lin,Wei Chen,Yu Yang.Analysis of DC bias exciting current of the single-phase transformer and its effect on protection[J].Power System Protection and Control,2010,38(24):158-162(in Chinese).
[14] 文俊,刘连光,项颂,等.地磁感应电流对电网安全稳定运行的影响[J].电网技术,2010,34(11):24-30.
Wen Jun,Liu Lianguang,Xiang Song,et al. Influences of geomagnetic induced currents on security and stability of power systems[J].Power System Technology,2010,34(11):24-30(in Chinese).
[15] 郭洁,黄海,唐昕,等.500 kV 电力变压器偏磁振动分析[J].电
网技术,2012,36(3):70-75.
Guo Jie,Huang Hai,Tang Xin,et al.Analysis on 500 kV power transformer vibration under DC magnetic biasing[J].Power System Technology,2012,36(3):70-75(in Chinese).
[16] Sablik M J,Burkhardt G L,Kwun H,et al.A model for the effect of stress on the low-frequency harmonic content of the magnetic induction in ferromagnetic materials[J].Journal of Applied Physics,1988,63(8):3930–3932.
[17] Jiles C.Theory of magnetomechanical effect[J].Journal of Physics D:Applied Physics,1995,28(8):1537-1546.
[18] Pengju Kang and D. Birtwhistle. Condition assessment of power transformer on-Load tap-changers using wavelet analysis[J]. IEEE Trans. Power Del, Vol. 16, No. 3, pp. 394–400, 2001.
[19] Pengju Kang and David Birtwhistle. Condition assessment of power transformer onload tap changers using wavelet Analysis and self-organizing map: field Evaluation[J]. IEEE Trans. Power Del, Vol. 18, No. 1, pp. 78–84, 2003.